Bi-directional speaker for voice alarm applications, certified according to EN 54-24, suitable for voice announcements and background music with excellent sound quality in buildings.
The 10W powered speaker is equipped with two 130mm full-range loudspeakers and a 100V line transformer with 4 power adjustments. A robust powder-coated aluminium housing in RAL 9010, and vandal-resistant feet ensure a permanent installation of this speaker. For additional reliability, a 2-pin ceramic block and a thermal fuse are provided and the speaker chassis is impregnated against wetness.
The speaker is also secured with the high protection class IP 65 against the risks of environmental influences.
Perfectly suitable for installation in corridors and hallways. The speaker is compliant with the British Standard BS 5839, Part 8.
Article No.: | 20122650 |
Product | DA 10-260/T-EN54 |
Power | 10/6/3/1,5 W |
Impedance (100V) | 1000/1667/3333/6667 ohm |
Frequency Range | 237 - 12.400 Hz |
Frequency Response | 79 - 17.500 Hz |
SPL 1W/1m, peak | 95,3 dB |
SPL 1W/4m, peak | 83,3 dB |
SPL Pmax/4m, peak | 93,3 dB |
SPL IEC268-5, 1W/1m | 89,0 dB |
SPL EN54-24, Pmax/4m | 86,0 dB |
Sensitivity EN54-24, 1W/1m | 89,6 dB |
Sensitivity EN54-24, 1W/4m | 77,0 dB |
Dispersion -6dB, 500Hz | h/v 2x130° |
Dispersion -6dB, 1KHz | h/v 2x150° |
Dispersion -6dB, 2KHz | h/v 2x145° |
Dispersion -6dB, 4KHz | h/v 2x75° |
Connector | 2-pin ceramic block |
Terminal diameter | 3,2 mm |
Maximum cable passage | 8 mm² |
Temperature range | -25 / +70 C° |
Dimensions | 201x176x160 mm |
Type A/B | B |
IP Rating | IP65 |
Weight (net) | 2,35 kg |
Colour | RAL 9010 |
Mounting | screws |
Packing Unit | 8 |
Ref. Nr. | 003-14 |
ID-Code | SAA-LS14 |
Certificate Number | 1438-CPR-1000 |
CE Year | 13 |
ic audio loudspeakers are tested and classified according to the IEC standard 60529 (degree of protection by enclosure) against the penetration of foreign objects and moisture. The classification is conforming to standards through characterization with a fixed code. This code consists of the letters IP (International Protection) followed by two digits. The first digit indicates the degree of protection against dust and the second digit the degree of protection against water. Please note that the testing of the products has been carried out in laboratory conditions which are not always 100% comparable with the conditions of different installation environments. This protection can be reduced due to normal wear and tear depending on the installation environment. RoHS compliant (2011/65/EU) The IP rating as well as the temperature range specified are based on ic audio test results, not on CNBOP-PIB test results. Certification only verifies the minimum requirements for EN54-24 compliance. |
Datasheet
Mounting Instructions
Tender specification
- DA_10-260T-EN54_en.pdf (English)